Special Features
High frequency, double conversion on-line UPS
Microprocessor based PWM technology
8 segment display for output and LED display
3 Phase in 3 Phase out
UPS start - up without battery and cold start
Short circuit protection, over load protection
Lightning and surge protection
SCR controlled convertor
Full out put isolation
Optional RS 232 interface, SNMP



Technical Specifications  
Power rating 10 KVA 20 KVA 30 KVA 45 KVA 60 KVA
Input Voltage 440V +/ - 20%
Frequency 50Hz+/- 2%
Phase Three
DC bus voltage 360 v dc
Out put Voltage 415 V +/ - 2%
Freq 50HZ + / - 0.2%
Phase Three
Wave form Pure Sine Wave
Transient response Within 3 cycles
THD <3 %
Crest factor 3:1 (Max)
Over load capacity 110% for 5 Minutes, 111 % -150% for 10 Seconds, > 150% - Shut Down
Noise Level < 55 dB at distance of 1 meter
Out put Isolation yes
Charger Voltage Selectable 110 to 120% of VDC
Current Selectable 7 % of battery capacity
Displays 8 Segment 8 segment display for voltage
LEDs main on, invertors on, dc on, over load, battery low, DC high,
Alarms Over load, Battery low, Shut down and on all errors
Communication port Rs 232, SNMP Optional